200 kVA Doosan Open Diesel Generator - ADE Doosan AD200D5

*Image for illustration purposes only, actual product may differ

ADE AD200D5 (Open)

200 kVA Three Phase Open Diesel Generator


  • Standby: 200 kVA / 160 kW
  • Prime: 180 kVA / 144 kW
  • Engine: Doosan P086TI
  • Alternator: Leroy Somer
  • Voltage: 400V
  • Frequency: 50Hz
  • Amps Per Phase: 288
  • Control Panel: Deep Sea 7320

Make an enquiry, call: +44 (0) 1977 657 982 or email: enquiries@ade-power.com for more information.

Options:


Additional Fuel Tank

Additional off-the-shelf or bespoke free-standing fuel tanks can be supplied to act as your generator's primary fuel source or to extend its total possible run time before the need to refuel.

Off-the-Shelf Fuel Tanks
Extended Base Fuel Tank

Extended base fuel tanks are bespoke designed & manufactured to suit the generator model & the capacity you require, extending the total possible run time before the need to refuel.

Bespoke Fuel Tanks
ATS Panel

ATS panels detect mains power failures and send a signal for the backup generator to start, transferring the load over to the generator once it has matched the correct voltage & frequency. Once mains power is restored, the panel will transfer the load back to the mains and shut down the generator.

ATS Panels
Bespoke Acoustic Enclosure

House this open generator in one of our bespoke designed & manufactured acoustic enclosures, reducing the noise level of the genset as well as protecting it from weather and other external environmental factors.

Acoustic Enclosures & Containers

ADE Doosan AD200D5 200 kVA Generator Specification

The ADE AD200D5 is a 200 kVA Three Phase Auto Start 50Hz Open Diesel Generator featuring the Doosan P086TI engine & a Leroy Somer alternator.

Generator Diesel Open 3 Phase 50Hz Standby Genset 200 kVA 150 kW ADE Doosan
Standby Power Rating 200 kVA / 160 kW
Prime Power Rating 180 kVA / 144 kW
Engine Doosan P086TI
Engine Governor Electronic
Engine Speed 1500 rpm
Alternator Leroy Somer
Voltage 400V
Frequency 50Hz
Amps Per Phase 288
Control Panel Deep Sea 7320
Connection Type Circuit Breaker
Circuit Breaker 4-Pole
Exhaust Emissions Level Unregulated
Base Fuel Tank Capacity 330 Litres
Fuel Consumption 38.1 litres per hour (at 100% load)
Dimensions (L x W x H) 2700mm x 1200mm x 1650mm
Dry Weight 1,837kg
Warranty 2 Years / 1000 Hours

Delivery Information

Worldwide delivery can be arranged for your product(s).

If you would like us to supply you with a price for delivery/shipping included in your quote then please let us know the final destination of your product(s) within your enquiry.

Please Note: Products can also be collected from our headquarters in South Kirkby, West Yorkshire, UK by yourself or your own choice of transportation, please get in touch to arrange.

Need Help?

There are 3 easy ways to find out more about this product:

*We aim to reply to all enquiries up to 5.00pm Mon-Fri. No replies on weekends or bank holidays. After which time, we will call you back the following working day.

For more information about the ADE AD200D5 Generator

Get in touch to speak with our experts